by NewPower Technologies


Intelligent protection of impressed current protection systems
against lightning and unstable power conditions

Description

SensorGuard™ by New Power Technologies detects imminent lightning events in the vicinity of your site and preemptively isolates your equipment from the AC supply, thus removing the possible surge path. It also detects when the AC supply voltage is damagingly high or low, and removes the grid connection until the supply voltage has stabilized.

SensorGuard delivers the level of protection that only preemptive isolation from the AC supply can provide. It complements existing Surge Protection Device (SPD) deployments. It is designed to trigger upon detection of Lightning activity only, and not to be triggered by normal electrically noisy environments, such as nearby wireless transmissions towers.

Features

  • Continually monitors AC power for instability.
  • Eliminates damage due to unstable power and peak load demand conditions.
  • Monitors for threatening atmospheric conditions (Lightning Ground Strike activity).
  • Eliminates fault current pathways through sensitive electronic circuits.
  • Proactive “Isolation” approach complements all SPD technologies.
  • Rugged design assures dependable protection in any environment.
  • Comes in both “Plug-N-Play” and “Hard Wired” configurations.
  • Low-maintenance modular design for “in field” service and upgrading.
  • Ideally suited for cathodic protection rectifier applications.

How SensorGuard Works

A control board continuously monitors the quality of the power grid. As abnormal voltage conditions are detected, the board opens a power contactor, thereby removing power from the equipment. It then automatically closes the contactor and restores power after a user defined period if no additional electrical threats are detected.

To minimize the risk of lightning induced surge damage, SensorGuard employs an external lightning sensor. This sensor continuously monitors the earth surface for approaching lightning ground strikes and causes the equipment to be isolated from AC power when these strikes are within a present setting such as 6 miles (10 km) from the sensor’s location.

The detection distance can be adjusted by the user. For pipeline systems, the sensitivity is usually adjusted to detect storms up to 20 miles (30 km) away, thus assuring maximum protection. The sensor is also unique in its ability to sense the build-up to a near or actual lightning strike by recognizing the “stepped leader event,” enabling SensorGuard to isolate equipment from AC power in advance of an actual lightning event.

Impressed current rectifiers used with pipeline systems are at particular risk from lightning surge currents because they stand electrically between the AC service and the pipeline and anode ground bed. SensorGuard will provide a high level of protection by physically disconnecting the rectifiers from the AC line during potentially damaging electrical events. The compact SensorGuard main unit can often be co-located in the rectifier panel.


 

SensorGuard Main Unit and SGLS Lightning Sensor

SensorGuard Models

SG01 for Single Phase Supplies
SG02 for Split (or Two) Phase Supplies
SG33 for Three Phase Supplies

All three models offer the full SensorGuard preemptive lightning protection, utilize the same board technology, come with the external SGLS Lightning Sensor, and monitor one phase of the AC supply for sustained low or high voltage levels. Standard contactors are rated 30 Amps. 60 or 90 Amp contactors are available for high-power, three-phase applications.

Model SG01: Single-Phase Configuration Guide

Part Number

Voltage Poles Contactors Wired

SG01/120V/3P/1C/HW
SG01/120V/3P/2C/HW
SG01/230V/3P/1C/HW
SG01/230V/3P/2C/HW

120 Vac
120 Vac
230 Vac
230 Vac
3
3
3
3
1
2
1
2
HW
HW
HW
HW

For Plug-N-Play, replace /HW by /PP. For rack-mount, add /RM.

Model SG02: Two-Phase Configuration Guide

Part Number

Voltage Poles Contactors Wired

SG02/120V/3P/1C/HW
SG02/120V/3P/2C/HW
SG02/230V/3P/1C/HW
SG02/230V/3P/2C/HW

120 Vac
120 Vac
230 Vac
230 Vac
4
4
4
4
1
2
1
2
HW
HW
HW
HW

For Plug-N-Play, replace /HW by /PP. For rack-mount, add /RM.

Model SG33 (same as SG03): Three-Phase Configuration Guide

Part Number

Voltage Poles Contactors Wired

SG33/120V/3P/1C/HW
SG33/120V/3P/2C/HW
SG33/230V/3P/1C/HW
SG33/230V/3P/2C/HW

120 Vac
120 Vac
230 Vac
230 Vac
4
4
4
4
1
2
1
2
HW
HW
HW
HW

For Plug-N-Play, replace /HW by /PP. For rack-mount, add /RM.

Ordering Options

  • Number of contactors

  • Contactor voltage (120 Vac, 230 Vac or custom)

  • Contactor current (30A, 60A, 90A or custom)

  • Hardwired or Plug-N-Play

Specifications
 

Model

SG01

SG02

SG03 / SG33

Number of phases

1

2

3

Voltage per phase, nominal

120 Vac or 230 Vac

Current per phase

30A motor load / 40A resistive

Power consumption, standby

18.8 W

21.5 W

21.5 W

Power consumption, protect mode

11 W

Steady-state DC isolation

> 12 kV

Operating temperature

-40°F to 150°F (-40°C to 65°C)

Fiber Optic input port

0.089 plastic fiber optic cable

Lightning Sensor range, typical

Approx. 5 - 20 miles (8 - 32 km)

Status indication

LEDs on Main Controller Board

Manual bypass

Bypass switch on Main Controller Board

Shipping weight

12 lbs (5.5 kg)

18 lbs (8.2 kg)

18 lbs (8.2 kg)

Shipping package dimensions

26" x 16" x 6" (660 x 407 x 152 mm)

Compliance

IEC/EN 61010 (CE Mark)

  

Cathodic Protection Products & Materials

  

Cathodic Protection Services

 Farwest Engineering
 Farwest Installation

  

Cathodic Protection of Offshore Structures

 Galvanic CP Systems
 Impressed CP Systems
 Attachment Systems
 Monitoring Equipment

  

Marine Products Division

 Marine ICCP Systems
 Galvanic CP Materials
 Marine Anti-Fouling
 Electrolytic De-Scaling
 Electro-Chlorination
 Marine CP Monitoring
 Galvanic Isolators

  

Corrosion Control Products Company

  

More Farwest
Website Resources

 Farwest News
 Search this Website
 Request Quote
 Order Products Online
 

Home

Products Services Search Request Quote Order Online

Farwest Corrosion Control Company
888-532-7937   (888-5FARWEST)
Complete Cathodic Protection™

Tel: 

 310-532-9524
Fax:  310-532-3934

1480 West Artesia Blvd., Gardena, CA 90248-3215, USA
 www.farwestcorrosion.com

© 1996-2009 Farwest Corrosion Control Company | Privacy Statement
 

Integrity – Service – Quality
                  
... Since 1956