GENERAL
The AC input of the
rectifiers shall be 115, 230 or 460 VAC – single or
three-phase – 60 Cycle.
ENCLOSURE
The rectifier case shall
be NEMA 4X, completely weatherproof for outdoor use. The
case shall be constructed of not less than eleven gauge
steel. All fabrication welds shall be clean and smooth.
The entire case shall be hot dip galvanized per
ASTM-123. The cabinet shall be equipped with an
instrument compartment welded to one end of the case
prior to galvanizing. This compartment shall house the
circuit breaker, output meters and the output terminals,
and shall have a hinged door and lockable stainless
steel latch. The lid on the oil chamber shall be hinged
on one side and have a minimum of four stainless steel
latches to provide a moisture proof seal. The gasket on
the lid shall be an oil-resistant neoprene sponge. On
rectifiers 500 watts and above, the transformer and
stack shall be mounted on separate removable racks in
the oil chamber. The internal horizontal panel on which
the voltage adjustment taps, AC input terminals and DC
terminals are mounted shall be at least four inches
below the recommended oil level as marked within the oil
chamber. All connecting wires from oil chamber to the
instrument compartment shall be sealed with an oil
resistant compound. These wires shall have a 1/2" gap in
the insulation above oil level to prevent siphoning.
Grounding lug to accommodate a #6 wire shall be provide
on the outside of the cabinet.
TRANSFORMER
The transformer shall be
specifically designed for use in a cathodic protection
rectifier, having separate primary and secondary copper
windings. Wire size on both windings is to be based on a
minimum of 1,000 circular mils per ampere. The material
used in the core of the transformers shall be of such
quality that core losses do not exceed 0.62 watts per
pound. The amount of core material shall be no less than
the amount given by the following formula:
AC = The square root
of the watts in the primary divided by 5.58
AC = The minimum core area in square inches, figured
as the cross sectional area of that portion of the
core which passes through the coil.
The transformer shall be
immersed in class F transformer varnish until all taps,
insulating materials, outer wrapping and coil windings
have been completely saturated. The transformer will
then be oven baked until completely dry.
When a three phase
rectifier is specified, it shall be provided with a
three phase transformer with three separate wound legs
or three separate transformers.
The secondary shall have
a sufficient number of coarse and fine taps to provide a
minimum of 18 equal step of adjustment. These taps shall
be brought out to link bar arrangement for adjusting the
output of the rectifier.
The link bars shall be
terminated on at least a 5/16" stud lug that has one end
drilled out so that the transformer tap wire can be
soldered to the back of the stud. Quick change plastic
knobs with brass inserts shall be used to connect the
link bars to the studs.
RECTIFYING ELEMENTS
The rectifier stack shall
consist of high current density selenium cell arranged
to give full wave rectification. Ratings shall be within
the manufacturer’s recommended current rating for
continuous operation with a 50°C ambient temperature.
The RMS voltage rating of the rectifier stack shall be
sufficient to withstand, without damage, the full output
of the transformer secondary when the load is
disconnected from the DC terminals, i.e., under open
circuit conditions.
When silicon is used as
the rectifying element, current rating for continuous
operation shall be for 50°C. ambient and the PRV rating
of the diodes shall be at least 1200 PIV. The diodes
shall be protected against high voltage surges with
selenium surge suppressors.
Current and voltage shall
be de-rated for higher ambient temperature, where
required, and in accordance with the manufacturers
recommendations.
PROTECTIVE DEVICES
The entire unit is to be
protected against overload and short circuit with a
fully magnetic circuit breaker of proper rating
connected between the AC supply and transformer primary.
Circuit breakers shall
have two poles for single phase units and three poles
for three phase units. In the case of silicon rectifiers
only, fuses shall be inserted in one leg of the AC
secondary of single phase units and in at least two of
the secondary legs of a three phase unit. All fuses
greater than 35 amps shall be bolt in style and shall
not rely on pressure type fuse holders.
DC METERS
One DC voltmeter and one
DC ammeter shall be provided. Each will have an accuracy
of 2% full scale. Hoyt # 17/3 meters or approved equal
shall have minimum scale lengths of 1-5/8". The ammeter
shall be connected to an external shunt with and
accuracy of at least 1%. The shunt shall be plainly
marked to show ampere rating and millivolt drop. This
shunt shall be mounted on the front panel of the
rectifier so as to be readily accessible for meter
accuracy checks.
DC TERMINALS
Solderless lugs rated for
full rectifier output current shall be provided for the
positive and negative output terminals of the rectifier
and shall be mounted on an insulated panel. Output
terminals shall be clearly identified on the panel as
"Positive" and "Negative".
WIRING & CONDUCTORS
All wiring within the
rectifier, except the meter circuits, shall be of the
high temperature motor lead wire with a minimum of 105°C
rating. Wire size shall be based on not less than 500
circular mils per ampere. All current carrying bolts,
terminals and connections made through the panel shall
be either soldered to the bolt head or made by use of
double nut method, so as not to depend on the
compression strength of the panel to maintain a tight
connection. Tap changing studs and output lugs shall be
a minimum of 5/16" diameter.
RECTIFIER DATA
Each rectifier shall be
provided with an engraved metal nameplate with the
following information.
1. Name
of manufacturer
2. AC input voltage
3. AC input amperes
4. AC frequency
5. Phase
6. DC output volts
7. DC output amperes
8. Ambient temperature in
°C.
In addition, a waterproof
envelope, placed in a suitable holder in the rectifier
door, shall contain a complete wiring diagram, operating
and maintenance manual and a copy of the test data
obtained on the final bench check out of the rectifier.
INSTRUMENT PANEL
Phenolic grade XXX, non
conductive, moisture resistant, specifically designed
for panel board use.
APPLICABLE
STANDARDS
The rectifiers shall meet
the appropriate sections of the following standards:
NEMA Publication No. MR 20-1958, reaffirmed by NEMA 1971
- Semiconductor Rectifiers, Cathodic Protection Units.
NEMA Standard Publication No. 250-1979, including Rev.
No. 1 – December 1980, Enclosures for Electrical
Equipment (1000 Volts maximum) |