GENERAL
The AC input of the
rectifiers shall be 115, 230 or 460 VAC – single or
three-phase – 60 Cycle.
ENCLOSURE
The cathodic protection rectifier case shall
be NEMA 3R, completely weatherproof for outdoor use. The
case shall be constructed of not less than eleven gauge
steel. All fabrication welds shall be clean and smooth.
The entire case shall be hot-dip galvanized per
ASTM-123. The cabinet shall be equipped with a suitable
pole mounting channel or base mounting legs welded to
the case prior to galvanizing. Screens in the
ventilation openings at the top and bottom of the case
shall be Stainless Steel. The front door shall be hinged
on one side and have a positive locking device capable
of taking a lock with a 3/8" diameter shank. In addition
to the front door, the left side panel of the case shall
be hinged and easily removable. The case shall have a
slide out rack assembly for accessibility. A grounding
lug to accommodate a #6 wire shall be provided on the
outside of the cabinet.
TRANSFORMER
The transformer shall be
specifically designed for use in a cathodic protection
rectifier, having separate primary and secondary copper
windings. Wire size on both windings shall be based on a
minimum of 1,000 circular mils per ampere. The material
used in the core of the transformers shall be of such
quality that core losses do not exceed 0.62 watts per
pound. The amount of core material shall be no less than
the amount given by the following formula:
AC = The square root of the watts in the primary divided
by 5.58 AC = The minimum core area in square inches, figured as
the cross sectional area of that portion of the core
which passes through the coil.
The transformer shall be
immersed in class F transformer varnish until all taps,
insulating materials, outer wrapping and coil windings
have been completely saturated. The transformer shall
then be oven baked until completely dry.
When a three-phase
rectifier is specified, it shall be provided with a
three-phase transformer with three separate wound legs
or three separate transformers.
The secondary shall have
a sufficient number of coarse and fine taps to provide a
minimum of 18 equal step of adjustment. These taps shall
be brought out to link bar arrangement for adjusting the
output of the rectifier.
The link bars shall be
terminated on at least a 5/16" stud lug that has one end
drilled out so that the transformer tap wire can be
soldered to the back of the stud. Quick-change plastic
knobs with brass inserts shall be used to connect the
link bars to the studs.
RECTIFYING ELEMENTS
The rectifier stack shall
consist of high current density selenium cell arranged
to give full-wave rectification. Ratings shall be within
the manufacturer’s recommended current rating for
continuous operation with a 50°C ambient temperature.
The RMS voltage rating of the rectifier stack shall be
sufficient to withstand, without damage, the full output
of the transformer secondary when the load is
disconnected from the DC terminals, i.e., under open
circuit conditions.
When silicon is used as
the rectifying element, current rating for continuous
operation shall be for 50°C ambient, and the PRV rating
of the diodes shall be at least 1200 PIV. The diodes
shall be protected against high voltage surges with
selenium surge suppressors.
Current and voltage shall
be derated for higher ambient temperature, where
required, and in accordance with the manufacturers
recommendations.
PROTECTIVE DEVICES
The entire unit shall be
protected against overload and short circuit with a
fully magnetic circuit breaker of proper rating
connected between the AC supply and transformer primary.
Circuit breakers shall
have two poles for single-phase units and three poles
for three-phase units. In case of silicon rectifiers
only, fuses shall be inserted in one leg of the AC
secondary of single-phase units and in at least two of
the secondary legs of a three-phase unit. All fuses
greater than 35 amps shall be bolt in style and shall
not rely on pressure type fuse holders.
DC METERS
One DC voltmeter and one
DC ammeter shall be provided. Each shall have an
accuracy of 2% full scale. Hoyt # 17/3 meters or
approved equal shall have minimum scale lengths of
1-5/8". The ammeter shall be connected to an external
shunt with an accuracy of at least 1%. The shunt shall
be plainly marked to show ampere rating and millivolt
drop. This shunt shall be mounted on the front panel of
the rectifier so as to be readily accessible for meter
accuracy checks.
DC TERMINALS
Solderless lugs rated for
full rectifier output current shall be provided for the
positive and negative output terminals of the rectifier
and shall be mounted on an insulated panel. Output
terminals shall be clearly identified on the panel as
"Positive" and "Negative".
WIRING &
CONDUCTORS
All wiring within the
rectifier, except the meter circuits, shall be of the
high temperature motor lead wire with a minimum of 105°C
rating. Wire size shall be based on not less than 500
circular mils per ampere. All current carrying bolts,
terminals and connections made through the panel shall
be either soldered to the bolt head or made by use of
double nut method, so as not to depend on the
compression strength of the panel to maintain a tight
connection. Tap changing studs and output lugs shall be
a minimum of 5/16" diameter.
RECTIFIER DATA
Each rectifier shall be
provided with an engraved metal nameplate with the
following information:
1. Name
of manufacturer
2. AC input voltage
3. AC input amperes
4. AC frequency.
5. Phase
6. DC Output volts
7. DC Output amperes
8. Ambient temperature in degrees C.
In addition, a waterproof
envelope, placed in a suitable holder in the rectifier
door, shall contain a complete wiring diagram, operating
and maintenance manual and a copy of the test data
obtained on the final bench check-out of the rectifier.
INSTRUMENT PANEL
Phenolic grade XXX,
non-conductive, moisture resistant, specifically
designed for panel board use.
APPLICABLE
STANDARDS
The rectifiers shall meet
the appropriate sections of the following standards:
NEMA Publication No. MR 20-1958, reaffirmed by NEMA
1971 - Semiconductor Rectifiers, Cathodic Protection
Units.
NEMA Standard Publication No. 250-1979, including Rev.
No. 1 – December 1980, Enclosures for Electrical
Equipment (1000 Volts maximum). |