|
|
FAQ
Frequently Asked Questions
by Dairyland Electrical
Industries


| Farwest places a high value
on getting our customers the information they need. If you have
questions of a technical nature regarding our products or
applications and cannot find the information on the website, please
phone us or email us at sales@farwestcorrosion.com. The
frequently asked questions below apply to Dairyland Electrical
Industries (DEI). |
How can the 3V threshold of a PCR
or 10V threshold of the ISP be adequate when I have 50V AC induced
onto my pipeline - won't the device instantly switch to the shorted
mode?
In a word: "No." - The reason that
the Dairyland device does not switch to the shorted mode is that the
device is a low impedance to the flow of alternating current. The
PCR AC impedance ranges from 0.005 to 0.010 ohm, while the ISP
varies between 0.088 ohm and 0.265 ohm, depending on the device
ratings. When the device is connected between a grounding system and
a pipeline with induced AC voltage, this low AC impedance path
instantly allows alternating current to flow and collapses the
induced AC voltage to below the device threshold. See the
application example regarding induced AC voltage.
What is the device threshold for
DC voltage versus AC voltage or other signals?
Dairyland devices have a threshold
that is an absolute voltage, which is the sum of DC plus peak AC
voltage, if AC is present. There are not separate thresholds for DC
versus AC. Normally, it is mainly DC voltage that contributes toward
the threshold of the product, as a device such as the models PCR,
PCRH, or ISP collapse any induced AC voltage to a small value, which
is the below the threshold (see question above). If the normal DC
voltage, measured across the two points to which the Dairyland
product will connect, is below the product threshold, the user will
normally not need to consider the small AC voltage contribution. The
only exception is the Dairyland model OVP, which blocks both AC and
DC voltage/current, and can be put into conduction if AC voltage is
present. See both the application information in the above question,
and data on the maximum DC voltage allowed in the application notes.
Do Dairyland devices need to be
put in series to achieve a higher threshold?
No. Unlike liquid-filled polarization
cells, which have a low threshold of around 1.3V, the Dairyland
model PCR has a 3V threshold, eliminating the need to place devices
in series. If a higher threshold is needed, consider either the
model ISP, which blocks to 10V or 17V, or contact Farwest for
other options. Most applications can be addressed with the standard
threshold values.
Are lightning and AC fault
current ratings equal?
No. Lightning has a unique waveform
that features a certain rise time to the peak value, and then decays
down over time. This waveform is defined for various voltage and
current scenarios, in documents such as ANSI C62.11. The most
commonly stated lightning current waveform is an 8x20 microsecond
characteristic. Dairyland devices have a stated peak value of 8x20
microsecond current capability. AC fault current has entirely
different, and consistent, properties compared to lightning. The
repetitive, sinusoidal waveform of an AC fault has predictable
energy values that can be used to calculate fault current ratings of
products. Most AC faults last approximately 3 to 5 cycles, until a
power breaker interrupts the fault current. The energy involved in
an AC fault is usually much higher than a typical lightning event,
in terms of how protective products should be rated. For these
reasons, Dairyland products have separate lightning and AC fault
ratings. For information on AC fault ratings needed for various
applications, see the AC fault application data.
|
|